REX Sensor - Part Number: REXM
The pdk Motion Request to Exit (REX) device is a perfect way to provide free egress by cutting power to a maglock. The REX sensor is specifically designed for indoor applications and features a passive infrared sensor with qualified motion analysis. The sensitivity of the REX sensor is easily adjusted for long- or short-range applications and features an adjustable time delay. Because of its sleek design, the REX sensor is easily mounted to any frame, header wall, or ceiling. The REX sensor is intended for indoor use only and is available in a white or brown enclosure.
REX devices are used in conjunction with access control systems to ensure that tenants are able to freely and safely exit an area. Options such as exit buttons, hands-free infrared, or touch-sensitive devices make a REX device an ideal choice for releasing maglocks or door strikes.
Specifications
Supply Voltage - 12 VDC - 24 VDC or VAC (50/60Hz)
Supply Current
- 18mA - 30mA at 12 VDC - 24 VDC
- 45mA - 80mA at 12 VAC - 24 VAC
Relay Output - 2C Contact (N.C/N.O) , 24 VDC 1Ah Max. 0.6 PFC
Detection Type - Passive Infrared
Relay Hold Time - 0.5 to 64 seconds
LED Indication - Red
Range - Coverage 12 x 5 ft. at 7 ft. hight / 30 x 12 ft. at 15 ft. high (Adjustment). Not evaluated by UL
Operating Temperature - -14° F to 131° F (-10° C to 55° C)
Weight - 0.4 lb. (0.18kg)
Humidity - 0 to 95% non-condensing
Dimensions - (W x H x D): 6.53 x 1.57 x 1.53 in. (166 x 40 x 39 mm)
Mounting Instructions
Select a mounting location over the center of the door or doors to be covered. The target must walk directly toward the detector. Mount the detector on the ceiling, wall, or door frame. The mounting height range is from 7 ft. to 15 ft.
Remove the front cover from the detector.
Route the wiring as necessary through the wiring entrance. For surface wiring, use the breakout wiring entrance on the front cover (at the same end as the wire entrance).
Loosely mount the back cover to the mounting surface using the supplied mounting screws.
Aim the detector for the desired coverage.
Mount the front cover on the detector. Choose between long-range and short-range detection patterns by adjusting the detector’s angle.
Long & Short Range Adjustment
The REX Sensor can be set to detect individuals at either a long range (several steps from the door) or at a short range (immediately in front of the door). If the building includes a lengthy approach to the exit doorway and there is no other foot traffic in the area, choose the long-range setting.
Setup and Testing
1. After mounting, apply power to the unit.
2. Wait at least 3 minutes for the detector to settle.
3. Test the unit by walking directly through the coverage area toward the door.
4. Aim the detector up or down if necessary to obtain the proper coverage.
5. Angle adjustment is from -20 degrees to 90 degrees.
6. Check that the relay latch time is sufficient. Adjust if necessary.
7. After confirming proper operation, replace the cover and perform a walk test one more time to ensure the coverage has not changed.
Detection Pattern
The figures below show the standard patterns for a wall-mounted unit. Rotate the lens to adjust the detect range (long range and short range).
Wiring
Terminal Wiring Diagram
- V+ - Power Connection (12 - 24 VDC/VAC)
- V- - Power Negative (Ground)
- NO - Normally Open
- NC - Normally Closed
- C - Common
CAUTION: Incorrect wiring will result in product damage.
Wiring a REX with a Mag Lock
-
Connect a wire from the Controller Port positive (+) terminal to the Mag Lock positive (+) terminal
- Connect a wire from the Mag Lock negative (-) terminal to the REX normally closed (NC) terminal
- Connect a wire from the Controller Relay Port normally closed (NC) terminal to the Rex common (C) terminal
- Connect a wire from the Controller Input block REX (B) terminal to the REX normally open (NO) terminal
DIP Switch Settings
DIP Switches 1, 2, 3 - Latch Time
DIP switches 1, 2, and 3 set the relay latch time. Latch time is the amount of time the relay remains active after the REX first detects motion. Latch time is adjustable from 0.5 sec to 64 seconds.
Table 1: Latch Time DIP Switch Settings
Time (seconds) |
Switch 1 |
Switch 2 |
Switch 3 |
0.5 (Default) |
OFF |
OFF |
OFF |
1 |
ON |
OFF |
OFF |
2 |
OFF |
ON |
OFF |
4 |
ON |
ON |
OFF |
8 |
OFF |
OFF |
ON |
16 |
ON |
OFF |
ON |
32 |
OFF |
ON |
ON |
64 |
ON |
ON |
ON |
DIP Switch 4 - LED
Table 2: DIP Switch Settings to enable/disable the LED
Switch 4 |
Function |
OFF |
Disabled |
ON |
Enabled (Default) |
When LED is enabled, it will flash on and off when first powered up. Once the flashing LED stops, the REX is ready to be used.
DIP Switch 5 - Relay Mode
Table 3: DIP Switch Settings for Relay Mode
Switch 5 |
Function |
OFF |
Fail Secure |
ON |
Fail-Safe (Default) |
A fail-secure locking device remains locked when power is lost.
A fail-safe locking device unlocks when power is lost.
DIP Switch 6 - Resettable / Non-resettable
Table 4: Resettable / Non-resettable DIP Switch Settings
Switch 6 |
Function |
OFF |
Non-resettable |
ON |
Resettable (Default) |
-
Resettable: The relay activates when the detector first sees motion. Any additional motion restarts the latch timer so the relay deactivates only when the detector no longer sees motion and the latch time has expired. Hint: This setting works best when bypassing a 24-hour contact.
-
Non-resettable: The relay activates when the detector first sees motion. It deactivates when the latch time ends, even if motion is still present. Hint: This setting works best when used with an access control system.
Troubleshooting and Maintenance
Trouble | Cause | Remedy |
REX does not power up | No or low input power. Input power polarity reversed. | Apply proper input voltageCorrect wiring polarity. |
Alarm LED does not light | LED jumper is set to LED OFFIncorrect sensor mounting height. | Set LED jumper to LED ENABLE Increase/decrease the mounting height. |
LED indicates light, no signal output | Incorrect wiring at output terminal lighting damage. | Correct the wiring faultReplace the sensor. |
The unit continues to operate after the input power has been disconnected. | The wire to the “V-” (Ground) power input was disconnected. The “V+” is still connected. | Disconnect wire from the “V+” power input. |
Installing a REX and Maglock to a Door Controller
System Events - REX Rules
Technical Support
Should you require any technical assistance, please contact our knowledgeable ProdataKey Support staff. Your support queries covering hardware, software installation, trouble tickets, troubleshooting, return merchandise authorization (RMA), or any other questions will be addressed as immediately as possible.
NOTE: In order to receive an RMA from pdk, we must first troubleshoot the device prior to the user receiving an RMA number and the device being returned to the user.
- Phone: 801.317.8802 option #2 or direct at: 801.206.4086
-
Email: support@prodatakey.com
- Direct Dealer Support Line: 801.206.4086
ProdataKey, LLC - 67 West 13490 South, Draper, Utah 84020 United States
Certifications
FCC Compliance Statement: This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
-
This device may not cause harmful interference.
- This device must accept any interference received, including interference that may cause undesired operation.
Product can be used without license conditions or restrictions in all European Union countries, including Austria, Belgium, Denmark, Finland, France, Germany, Greece, Ireland, Luxembourg, The Netherlands, Portugal, Spain, Sweden, and the United Kingdom, as well as other non-EU countries, including Iceland, Norway, and Switzerland.
Copyright
© 2021 ProdataKey, LLC. All rights reserved. ProdataKey, the ProdataKey logo, and other ProdataKey marks are owned by ProdataKey, LLC and may be registered. All other trademarks are the property of their respective owners. ProdataKey assumes no responsibility for any errors that may appear in this manual. Information contained herein is subject to change without notice.
REX Sensor Installation Manual
ProdataKey Controllers/Readers
© 2021 ProdataKey, LLC.
Ver: 20191114
Date: November 14, 2019
Doc No. REXM-IM-001